Insulators

Anti-Contamination

Introduction

1. Problems of Contaminated Insulator

When an insulator is polluted and wetted,

  • Reduction of withstand voltage causes flashover accidents
  • Erosion of glass insulators by increased leakage current
  • Electrolytic corrosion in metal fittings => Zinc Sleeve

Problems of Contaminated Insulator

Erosion

2. Type of Contamination

  • Marine Contamination: Sea salt, NaCl is main chemical component
  • Desert Contamination: Salt in sand & deposits of insoluble material
  • Industrial & Agricultural Contamination: Cement, soot and etc.

Type of Contamination

Corrosion

Page top

3. Flashover Mechanism

  • Dry band formation near cap and pin by high density of leakage current
  • Partial discharge at dry band
  • Development into overall flashover

Flashover Mechanism1

Flashover Mechanism2

Flashover Mechanism3

4. Influence of Contaminants

  • NaCl shows the lowest withstand voltage among soluble material.
  • Withstand voltage decreases with amount of non-soluble material, which retains moisture in the contamination layer.

Influence of Contaminants1

Influence of Contaminants2

5. Evaluation of Contamination Performance

  • Clean fog method is recommended test, because it provides almost minimum envelope curve of test results on naturally contaminated insulators.
  • Shed profile is designed by numerous contamination test results, including actual scale insulator string in High Voltage Laboratory

Evaluation of Contamination Performance1

Evaluation of Contamination Performance2

6. Anti-Contamination Design Procedures

Anti-Contamination Design Procedures

Page top

7. Countermeasures against Contamination Problems

There are several countermeasures against contamination problems based on environmental condition, type of contaminants and cost.

A) Suspension (Disc) Insulators

(1) Increase leakage distance

For type Insulator

For type Insulator

(2) To prevent contamination accumulation

Aero-dynamic type Insulator

Aero-dynamic type Insulator

For type Insulator

Outer-rib type Insulator

Outer-rib type Insulator

(3) To prevent dry band formation

Semiconducting glaze Insulator

Semiconducting glaze Insulator

B) Station Post & Hollow Insulators

(1) Increase leakage distance

Plain shed

Plain shed

Single rib shed

Single rib shed

Double rib shed

Double rib shed

Alternating shed

Alternating shed

(2) To prevent dry band formation

Semiconducting Glaze Insulators with various shed profile

Inquiry about Technical Information

Please apply with the contact form and give us your comments or questions.