Insulators

Anti-Contamination

Semiconducting Glaze (SCG) Insulator (DURASSTOR®)

NGK supply Suspension (Disk), Line Post and Station Post Insulators coated with semiconducting glaze.

Introduction

  • Tin-oxide system glaze including niobium oxide
  • Current flowing through semiconducting glaze
    » Surface drying effect by Joule's heat
    » Uniform (resistive) voltage distribution

When contaminated surface is moistened, leakage current flows in wetted contaminant. And then non-uniform current density forms dry band.

Semicoducting Glaze Insulator

Normal type for light contamination

Normal type for light contamination

→

DC Fog type for DC transmission line

DC Fog type for DC transmission line

Ordinary Glaze Insulator

Partial arc at dry band

Partial arc at dry band

» Radio & TV noise Overall Flashover

Features

  • Excellent Anti-Contamination Performance: Withstand voltage of SCG insulators is higher than that of polymer and ceramic insulators.
  • Excellent Corona Suppression Characteristics: No corona discharge even in heavy contamination condition.
  • Long Term Performance confirmed by service experience.

Contamination Test

Contamination Test

161kV Transmission Line

161kV Transmission Line

Inquiry about Technical Information

Please apply with the contact form and give us your comments or questions.